2 Functions of Devices in DVP-PLC
DVP-PLC Application Manual
2-39
Special
M
Function
ES
EX
SS
SA
SX
SC
EH
EH2
SV
Off
Ø
On
STOP
Ø
RUN
RUN
Ø
STO
P
Attribute Latched Default
M1134*
Special high-speed pulse output Y0 (50KHz)
On: continuous output
(Not available in SC_V1.4 and above)
Off Off - R/W NO Off
M1135*
Special high-speed pulse output Y0 (50KHz)
reaches the target number of pulses.
SC_V1.4 and above: 2-axis synchronous control,
enabling Y11 output
Off Off Off R/W NO Off
M1136* Retaining the communication setting of COM3
Off - - R/W NO Off
M1138*
Retaining the communication setting of COM1
(RS-232), modifying D1036 will be invalid when
M1138 is set.
Off - - R/W NO Off
M1139*
Selecting ASCII or RTU mode of COM1 (RS-232)
when in Slave mode
Off: ASCII; On: RTU
Off - - R/W NO Off
M1140 MODRD/MODWR/MODRW data receiving error
Off Off - R NO Off
M1141 MODRD/MODWR/MODRW parameter error
Off Off - R NO Off
M1142 Data receiving of VFD-A commands error
Off Off - R NO Off
M1143*
Selecting ASCII or RTU mode of COM2 (RS-485)
when in Slave mode
Off: ASCII; On: RTU
Selecting ASCII or RTU mode of COM2 (RS-485)
when in Master mode (used together with MODRD/
MODWR/MODRW instructions)
Off: ASCII; On: RTU
Off - - R/W NO Off
M1144*
Switch for enabling adjustable pulse
accelerating/decelerating output Y0
Off Off Off R/W NO Off
M1145* Adjustable pulse output Y0 is accelerating
Off Off - R/W NO Off
M1146*
Adjustable pulse output Y0 reaches the target
frequency
Off Off - R/W NO Off
M1147* Adjustable pulse output Y0 is decelerating
Off Off - R NO Off
M1148* Adjustable pulse output Y0 is completed
Off Off Off R/W NO Off
M1149*
Adjustable pulse output Y0 temporarily stops
counting the number of pulses.
Off Off - R/W NO Off
M1150
DHSZ instruction in multiple set values comparison
mode
Off - - R/W NO Off
M1151
The execution of DHSZ multiple set values
comparison mode is completed.
Off - - R NO Off
M1152
Setting up DHSZ instruction as frequency control
mode
Off - - R/W NO Off
M1153 DHSZ frequency control mode has been executed.
Off - - R NO Off