Delta-electronics Programmable Logic Controller DVP-PLC Manuel d'utilisateur Page 397

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 586
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 396
7 Application Instructions API 50-99
DVP-PLC APPLICATION MANUAL
7-113
Example 3: Diagram of using PID instruction in temperature control (S
3
+ 4 = 1)
PID
Temperature instruction (SV)
Heating (MV)
Actual temperature
(PV)
Heater
Temperature
detection
device
Example 4: How to adjust PID parameters
Assume that the transfer function of the controlled device G(S) in a control system is a first-order function
()
a
s
b
sG
+
=
(most models of motors are first-order function), SV = 1, and sampling time (T
S
) = 10ms, we
suggest you to follow the steps below for adjusting the parameters.
Step 1: Set K
I
and K
D
as 0 and K
P
as 5, 10, 20 and 40. Record the SV and PV respectively and the results
are as the figure below.
1.5
1
0.5
0
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1
K =40
P
K =20
P
K =10
P
SV=1
K =5
P
Time (sec)
Step 2: From the figure, we can see that when K
P
= 40, there will be over-reaction, so we will not select it.
When K
P
= 20, the PV reaction curve will be close to SV and there will not be over-reaction, but due to its
fast start-up with big transient MV, we will consider to put it aside. When K
P
= 10, the PV reaction curve will
get close to SV value more smoothly, so we will use it. Finally when K
P
= 5, we will not consider it due to the
slow reaction.
Step 3: Select K
P
= 10 and adjust K
I
from small to big (e.g. 1, 2, 4 to 8). K
I
should not be bigger than K
P
.
Adjust K
D
from small to big (e.g. 0.01, 0.05, 0.1 and 0.2). K
D
should not exceed 10% of K
P
. Finally we
obtain the figure of PV and SV below.
Vue de la page 396
1 2 ... 392 393 394 395 396 397 398 399 400 401 402 ... 585 586

Commentaires sur ces manuels

Pas de commentaire