2 Functions of Devices in DVP-PLC
DVP-PLC Application Manual
2-35
Special
M
Function
ES
EX
SS
SA
SX
SC
EH
EH2
SV
Off
Ø
On
STOP
Ø
RUN
RUN
Ø
STO
P
Attribute Latched Default
M1030*
ES/SA: Y1 pulse output of PLSY, PLSR instructions
is completed, or other relevant instructions complete
their executions.
EH/EH2/SV: the 2
nd
group pulse output CH1 (Y2,
Y3) is completed, or other relevant instructions
complete their executions.
Off - - R NO Off
M1031* Clear all non-latched areas
Off - - R/W NO Off
M1032* Clear all latched areas
Off - - R/W NO Off
M1033* Memory latched when STOP
Off - - R/W NO Off
M1034* Disabling all Y outputs
Off - - R/W NO Off
M1035*
Enabling input point X as the RUN/STOP switch,
corresponding to D1035
(SA designates X7 only; SX designates X3 only; SC
designates X5 only)
- - - R/W YES Off
EH2/SV: the 3
rd
group pulse output CH2 (Y4, Y5) is
completed. (Not available in EH)
Off - - R NO Off
M1036
SPD instruction is able to use X0 ~ X5 to detect the
flag (only available in SC_V1.4 and above)
Off Off - R/W NO Off
M1037
EH2/SV: the 4
th
group pulse output CH3 (Y6, Y7) is
completed. (Not available in EH)
Off - - R NO Off
M1039* Fixing time scan mode
Off - - R/W NO Off
M1040 Disabling step
Off - - R/W NO Off
M1041 Starting step
Off - Off R/W NO Off
M1042 Enabling pulses
Off - - R/W NO Off
M1043 Zero return completed
Off - Off R/W NO Off
M1044 Zero point condition
Off - Off R/W NO Off
M1045 Diabling all output reset
Off - - R/W NO Off
M1046 Setting STL status as On
Off - - R NO Off
M1047 Enabling STL monitoring
Off - - R/W NO Off
M1048 Alarm status
Off - - R NO Off
M1049 Setting up alarm monitoring
Off - - R/W NO Off
M1050 Inhibiting I001
Off - - R/W NO Off
M1051 Inhibiting I101
Off - - R/W NO Off
M1052 Inhibiting I201
Off - - R/W NO Off
M1053 Inhibiting I301
Off - - R/W NO Off
M1054 Inhibiting I401
Off - - R/W NO Off
M1055 Inhibiting I501
Off - - R/W NO Off