9 Application Instructions API 150-199
DVP-PLC Application Manual
9-13
API Mnemonic Operands Function
154
RAND P
Random Number
Controllers
ES/EX/SS SA/SX/SC EH/SV
Bit Devices Word Devices Program Steps Type
OP
X Y M S K H KnX KnY KnM KnS T C D E F
S
1
* * * * * * * * ***
S
2
* * * * * * * * ***
D
* * * * * ***
RAND, RANDP: 7 steps
PULSE 16-bit 32-bit
ES EX SS SA SX SC EH SV ES EX SS SA SX SC EH SV ES EX SS SA SX SC EH SV
Operands:
S
1
: Lower bound of the random number S
2
: Upper bound of the random number D: The random number
produced
Explanations:
1. S
1
S
2
; K0 S
1
, S
2
K32,767
2. See the specifications of each model for their range of use.
3. Entering S
1
> S
2
will result in operation error. The instruction will not be executed at this time, M1067, M1068 =
On and D1067 records the error code 0E1A (hex).
Program Example:
When X10 = On, RAND will produce the random number between the lower bound D0 and upper bound D10 and
store the result in D20.
X10
RAND
D0 D10
D20