7 Application Instructions API 50-99
DVP-PLC APPLICATION MANUAL
7-31
Program Example 1:
M1000
DPLSY K1000 K1000
EI
FEND
Y0
I 001
IRET
SET M1347
M1000
DPLSY K1000 K1000 Y2
I 101
IRET
SET M1348
END
Explanations:
a) Whenever X0 is triggered, Y0 will output 1,000 pulses; whenever X1 is triggered, Y2 will output 1,000 pulses.
b) When X triggers Y pulse output, there should be an interval of at least one scan time between the end of Y
pulse output and the next X-triggered output.
Program Example 2:
X1
M1347
PLSY K1000 K1000 Y0
X2
END
Explanations:
When both X1 and X2 are On, Y0 pulse output will keep operating. However, there will be a short pause (approx.
1 scan time) every 1,000 pulses before the output of the next 1,000 pulses.