Delta-electronics Programmable Logic Controller DVP-PLC Manuel d'utilisateur Page 64

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 586
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 63
2 Functions of Devices in DVP-PLC
DVP-PLC Application Manual
2-36
Special
M
Function
ES
EX
SS
SA
SX
SC
EH
EH2
SV
Off
Ø
On
STOP
Ø
RUN
RUN
Ø
STO
P
Attribute Latched Default
M1056
Inhibiting I6□□
Off - - R/W NO Off
M1057
Inhibiting I7□□
Off - - R/W NO Off
M1059 Inhibiting I010 ~ I060
Off - - R/W NO Off
M1060 System error message 1
Off - - R NO Off
M1061 System error message 2
Off - - R NO Off
M1062 System error message 3
Off - - R NO Off
M1063 System error message 4
Off - - R NO Off
M1064 Incorrect use of operands
Off Off - R NO Off
M1065 Syntax error
Off Off - R NO Off
M1066 Loop error
Off Off - R NO Off
M1067* Calculation error
Off Off - R NO Off
M1068* Calculation error locked (D1068)
Off - - R NO Off
M1070
ES/SA: Y1 time base switching for PWM instruction
(On: 100us; Off: 1ms)
EH/EH2/SV: Y0 time base switching for PWM
instruction (On: 100us; Off: 1ms)
EH_V1.2 and above/EH2/SV: when On, D1371 will
decide the time base)
Off - - R/W NO Off
M1071
Y2 time base switching for PWM instruction (On:
100us; Off: 1ms)
EH_V1.2 and above/EH2/SV: when On, D1372 will
decide the time base)
Off - - R/W NO Off
M1072 Executing PLC RUN instruction
Off On Off R/W NO Off
M1075 Error occurring when writing FLASH card
Off - - R NO Off
M1076* Real time clock malfunction
Off - - R NO Off
M1077 Battery in low voltage, malfunction or no battery
Off - - R NO Off
M1078
Immediately stopping Y0 pulse output for PLSY
instruction
Off - - R/W NO Off
M1079
Immediately stopping Y1 pulse output for PLSY
instruction
Off - - R/W NO Off
M1080 Requesting COM2 monitoring
Off - - R NO Off
M1081 Changing direction for FLT instruction
Off - - R/W NO Off
M1082 Real time clock has been changed
Off - - R NO Off
M1083
Allowing interruption subroutine in FROM/TO
instructions
Off - - R/W NO Off
M1084*
Detecting bandwidth (only available in
ES/EX/SS_V6.4, SA/SX_V1.6, SC_V1.4 and above)
Off Off Off R/W NO Off
Vue de la page 63
1 2 ... 59 60 61 62 63 64 65 66 67 68 69 ... 585 586

Commentaires sur ces manuels