7 Application Instructions API 50-99
DVP-PLC APPLICATION MANUAL
7-115
The example program of the instruction delay:
M1002
MOV K10 D3
M0
TMR T0 D3
T0
RST T0
MOV K50 D2D1D0>
MOV K-50 D2D1D0<
MOV K0 D2D1D0=
ADD D2 D1 D1
M10
CMP D2 K0 M10
D0D1<
MOV D0 D1
M12
D0D1>
MOV D0 D1
M0
PID D1 D1116 D10 D5
Application 2 Speed control system and pressure control system work individually (use diagram of Example 2).
Purpose: After the speed control operates in open loop for a period of time, adding into it the pressure control system
(PID instruction) for close loop control.
Explanation: Since the speed and pressure control systems are not interrelated, we have to structure a open loop for
speed control first following by a close loop pressure control. If you fear that the control instruction of the
pressure control system changes too fast, you can consider to add the instruction delay illustrated in
Application 1 into the control. See the control diagram below.
D40
0
255
0rpm
3,000rpm
D30
D32 D1116
D31
+
+
M3
PID
PV
MVD5
D1
SV
D0
D1110
Speed
instruction
M2 = On
Speed
converted
to
voltage
AC
motor
drive
MV converted to
accel/decel value
M0 = On
Pressure
instruction
Delay
(optional)
M1 = On
Pressure
meter