7 Application Instructions API 50-99
DVP-PLC APPLICATION MANUAL
7-38
1 ~ 5,000ms 1 ~ 5,000ms
16-bit instruction: 110 ~ 32,767PLS
32-bit instruction: 110 ~ 2,147,483,647PLS
Frequency F
Maximum speed: 10 ~ 200,000Hz
Decel timeAccel time
F0
Start
frequency
Total number of output pulses
3. The acceleration/deceleration of EH/EH2/SV series MPU is based on the number of pulses. If the output cannot
reach the maximum acceleration frequency within the acceleration/deceleration time offered, the instruction will
automatically adjust the acceleration/deceleration time and the maximum frequency.
4. The operands have to be set before the execution of the instruction.
5. All acceleration/deceleration instructions are included with the brake function. The brake function will be
enabled when PLC is performing acceleration and the switch contact is suddenly Off. The deceleration will
operate at the slope of the acceleration.
S
1
F
0
Time T
Frequency F
Original acceleration path
Brake path