Train ing Kit O peratio n Manua l
1-2
1.1 Introduction of DVP12SE
DVP-SE is a 12-point (8 DI+4 DO) PLC MPU, offering various instructions and with 16K steps
program memory, able to connect to all DVP Slim type series extension modules and high-speed
extension modules, including digital I/O (max. 480 I/O points) and analog modules (for A/D, D/A
conversion and temperature measurement). 2 points of 100 kHz and 2 points of 10 kHz high-speed
pulse output satisfy all kinds of applications. DVP-SE is small in size, and can be installed easily.
Users do not have to install any batteries in DVP-SE series PLCs. The PLC programs and the
latched data are stored in the high-speed flash memories.
1. Setting the Ethernet
The DVP-SE series PLC contains a built-in Ethernet communication port. Users have to set the
network parameter before the PLC connects to other network devices. The default parameter
setting values are 192.168.1.5 (the IP address) and 255.255.255.0 (the subnet mask). Users
can set the parameter by using DCISoft, or by using the PLC program to write the values into
the network control register (CR).
Software: Start the DCIsoft, and connect the PC to the DVP-SE series PLC through the
ehternet cable. Enter “Communication Setting” page in DCISoft, and choose “Ethernet”
communication port. Then, click “Search” to search for the picture representing the DVP-SE
series PLC. After users click the picture twice, the setting page appears. Finally, enter the
related parameters, and click “Apply” to finish the setting.
PLC program: Users use the instruction “To” to write the IP address (CR#88, 89) and the
subnet mask (CR#90, 91). For example, when the IP address is 192.168.1.5, users write
192.168 (H’C0A8) into CR#89, and .1.5 into CR#88 (H’105).
Note: When users use the instruction “From/To” to read the data from the network control
register and write the data into it, the module number is K108.
2. Specifications
Program capacity: 16k steps/Data register: 12k words
Higher execution speed compared to the competition: LD: 0.64µs, MOV: 2µs
Built-in Ethernet supports MODBUS TCP and Ethernet/IP
IP Filter function is a firewall that offers the first line of defense and provides protection from
malware and network threats
Supports DVP-S series left-side and right-side modules
No battery required. Maintenance-free.
(Real time clock operates for 15 days after power off)
3. Motion control functions
4 setos of high-speed pulse output: 100 kHz/2 sets, 10 kHz/2 sets
8 sets of high-speed pulse input: 100 kHz/2 sets, 10 kHz/6 sets
Supports 2-axis linear and arc interpolation
4. Built-in High-speed Counters
1-phase 1 input 1-phase 2inputs 2-phase 2 inputs
Sets Bandwidth Sets Bandwidth
Sets Bandwidth
2/6 100 kHz/10 kHz 2 100 kHz 1/3 50 kHz/5 kHz