VFD-S Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
Preface
Thank you for choosing DELTA’s high-performance VFD-S Series. VFD-S Series are
manufactured by adopting high-quality components, material and incorporating the latest
microprocessor technology available.
Getting Started
This manual will be helpful in the installation, parameter setting, troubleshooting, and daily
maintenance of the AC motor drives. To guarantee safe operation of the equipment, read
the following safety guidelines before connecting power to the AC motor drives. Keep
this operating manual handy and distribute to all users for reference.
!
WARNING
!
Always read this manual thoroughly before using VFD-S series AC Motor Drives.
!
DANGER! AC input power must be disconnected before any maintenance. Do not
connect or disconnect wires and connectors while power is applied to the circuit.
Maintenance must be performed by qualified technicians.
!
CAUTION! There are highly sensitive MOS components on the printed circuit boards.
These components are especially sensitive to static electricity. To avoid damage to
these components, do not touch these components or the circuit boards with metal
objects or your bare hands.
!
DANGER! A charge may still remain in the DC-link capacitor with hazardous voltages
even if the power has been turned off. To avoid personal injury, please ensure that
power has turned off before operating AC drive and wait ten minutes for capacitors to
discharge to safe voltage levels.
!
CAUTION! Ground the VFD-S using the ground terminal. The grounding method must
comply with the laws of the country where the AC drive is to be installed. Refer to Basic
Wiring Diagram (Chapter 3).
!
CAUTION! The final enclosures of the AC drive must comply with EN50178. (Live parts
shall be arranged in enclosures or located behind barriers that meet at least the
requirements of the Protective Type IP20. The top surface of the enclosures or barrier
that is easily accessible shall meet at least the requirements of the Protective Type
IP40). (VFD-S series corresponds with this regulation.)
!
CAUTION! The rated voltage of power system that is installed on AC drive must be
equal to or less than 240 Volts (460V model is 480 Volts) and the current must be equal
to or less than 5000A RMS.
!
DANGER! The AC drive may be destroyed beyond repair if incorrect cables are
connected to the input/output terminals. Never connect the AC drive output terminals
U/T1, V/T2, and W/T3 directly to the AC main circuit power supply.
CAUTION! Heat sink may heat up over 70 (158), during the operation. Do not
touch the heat sink.
Vue de la page 0
1 2 3 4 5 6 ... 142 143

Résumé du contenu

Page 1 - Preface

VFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED Preface Thank you for choosing DELTA’s high-performance VFD-S Series. VFD-S Series are manu

Page 2

2 VFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 2-32.4 Connections DANGER Hazardous Voltage Before accessing the AC drive:  Disconnect

Page 3 - TABLE OF CONTENTS

8 VFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 8-3 Group 2 Operation Method Parameters Parameters Explanation Settings Factory Setting

Page 4

VFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 8-4 Parameters Explanation Settings Factory Setting 2-01 Source of Operation Command d0: b

Page 5

8 VFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 8-5 Group 3 Output Function Parameters Parameters Explanation Settings Factory Setting 3

Page 6 - Serial Number & Bar Code

VFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 8-6 Group 4 Input Function Parameters Parameters Explanation Settings Factory Setting 4-00 P

Page 7

8 VFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 8-7 Parameters Explanation Settings Factory Setting 4-09 Line Start Lockout d0: Disable

Page 8

VFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 8-8 Group 5 Multi-Step Speed and PLC Parameters Parameters Explanation Settings Factory Set

Page 9

8 VFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 8-9 Group 6 Protection Parameters Parameters Explanation Settings Factory Setting d0: Dis

Page 10 - VFD-S Series

VFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 8-10 Group 7 Motor Parameters Parameters Explanation Settings Factory Setting 7-00 Motor Ra

Page 11 - DIVISION

8 VFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 8-11 Group 9: Communication Parameters Parameters Explanation Settings Factory Setting 9

Page 12

VFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 8-12 Group A: Communication Parameters Parameters Explanation Settings Factory Setting A-00

Page 13

VFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 2-42.5 Environments Avoid rain and moisture, Avoid direct sunlight, Avoid corrosive gases or

Page 14 - CHAPTER 3 WIRING

AVFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED A-1STANDARD SPECIFICATIONS Voltage Class 115V Class 230V Class 460V Class Model Number V

Page 16 - PNP (source mode)

BVFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED B-1 ACCESSORIES B.1 Non-fuse Circuit Breaker Chart Per UL 508C, paragraph 44.8.6, part a,

Page 17

VFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED B-2B.2 Braking Resistor and Unit chart for use with all Delta AC Drives Applicable Motor Vol

Page 18

BVFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED B-3 Braking Resistor Dimensions Unit: mm (inch) TYPE L1 L2 H D W MAX. WEIGHT (g)MVR200W1

Page 19

VFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED B-4 B.3 EMI Filters The DELTA VFD-S Series 0.25-3HP, 115V, 230V, 460V AC drive uses DELTA EMI

Page 20 - Multi-step speed 3

BVFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED B-5 EMI Filter (RF022S21BA / RF022S43BA) 27(1.06)50(1.97)228(8.98)15(0.59)24(0.94)100(3.94)

Page 21

VFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED B-6EMI Filter (12DKT1W3S) POWER-IN EMI Filter (08TDT1W4S)

Page 22

BVFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED B-7 EMI Filter (22DRT1W3S) POWER-IN EMI Filter (20TDT1W4S)

Page 23

VFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED B-8EMI Filter (35DRT1W3C) POWER-IN

Page 24 - STOP/RESET

2 VFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 2-5 Reinstall Division Plate. Screw Torque: 5 to 6 kgf-cm (4.3 to 5.2 in-lbf) For Optiona

Page 25

BVFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED B-9 B.4 Din Rail-DR01 Units: mm Models Screw Size VFD002S11A/B M4*22 VFD002S21A/B/E M4*22

Page 26

VFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED B-10B.5 Remote Controller RC-01 Unit: mm (inch) AFM GND +10VAVI GNDM2M0 M1 M3865416

Page 27 - 4.4 Keypad Operation

BVFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED B-11 B.6 Conduit Bracket (BK-S) Unit: mm (inch) 22.0(0.87)22.0(0.87)28.0(1.1)67.8(2

Page 28

VFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED B-12B.7 Zero Phase Reactor (RF220X00A) Recommended Wire Size Cable type (Not

Page 29

CVFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED C-1 Dimensions VFD002S11A 0.25HP 115V / 1 Phase VFD002S21A 0.25HP 230V / 1 Pha

Page 30

VFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED C-2VFD002S11B 0.25HP 115V / 1 Phase VFD002S21B 0.25HP 230V / 1 Phase VFD002S23B 0.25

Page 31

CVFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED C-3 VFD002S21E 0.25HP 230V / 1 Phase VFD004S21E 0.5HP 230V / 1 Phase VFD007S21E

Page 32

VFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED C-4VFD004S11A 0.5HP 115V / 1 Phase VFD004S21A 0.5HP 230V / 1 Phase VFD004S23A 0.5HP

Page 33

CVFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED C-5 VFD004S11B 0.5HP 115V / 1 Phase VFD004S21B 0.5HP 230V / 1 Phase VFD004S23B 0.5

Page 34

VFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED C-6VFD004S43A/E 0.5HP 460V / 3 Phase VFD007S21A 1 HP 230V / 1 Phase VFD007S23A 1

Page 35

VFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 2-6UL Enclosed Type RS485 RJ11PLUGRJ11JACKSCREWClose the cover and tighten screw as shown

Page 36

CVFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED C-7 VFD004S43B 0.5HP 460V / 3 Phase VFD007S21B 1 HP 230V / 1 Phase VFD007S23B

Page 37 - (3), (4) Enabling S curve

VFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED C-8VFD007S43A/E 1 HP 460V / 3 Phase Unit: mm [inches] 11.1 [0.44]5.0 [0.20]3.0 [0.12]12

Page 38

CVFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED C-9 VFD007S43B 1 HP 460V / 3 Phase Unit: mm [inches] 5.0 [0.20]11.1 [0.44]67.8 [2.67]

Page 39

VFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED C-10VFD007S11A 1 HP 115V / 1 Phase Unit: mm [inches] 86.5 [3.41]100.0 [3.94]129.0 [5.08

Page 40 - Current signal input(4-20mA)

CVFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED C-11 VFD007S11B 1 HP 115V / 1 Phase Unit: mm [inches] 86.5 [3.41]100.0 [3.94]73.0 [2.

Page 41

VFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED C-12VFD015S21A 2 HP 230V / 1 Phase VFD015S23A 2 HP 230V / 3 Phase Unit: mm [inches]

Page 42

CVFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED C-13VFD015S21D/E 2 HP 230V / 1 Phase VFD022S21D/E 2 HP 230V / 1 Phase VFD022S23D

Page 43

VFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED C-14VFD015S43A/E 2 HP 460V / 3 Phase VFD022S23A 3 HP 230V / 3 Phase VFD022S43A/E

Page 44

CVFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED C-15VFD015S21B 2 HP 230V / 1 Phase VFD015S23B 2 HP 230V / 3 Phase VFD015S43B

Page 45

VFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED C-16VFD022S21A 3 HP 230V / 1 Phase Unit: mm [inches] 1.0 [0.04]5.5 [0.22]9.5 [0.38]130.

Page 46

3 VFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 3-1CHAPTER 3 WIRING 3.1 Basic Wiring Diagram Users must connect wiring according to the

Page 47

CVFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED C-17VFD022S21B 3 HP 230V / 1 Phase Unit: mm [inches] 1.0 [0.04]5.5 [0.22]9.5 [0.38]130

Page 49 - Potentiometer Scale

DVFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED D-1 DELTA ELECTRONICS, INC. EC Declaration of Conformity According to the Low Volta

Page 50

VFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED D-2 DELTA ELECTRONICS, INC. EC Declaration of Conformity According to the Electromagnetic

Page 51

VFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 3-2 For VFDXXXSXXE NPN (sink mode) B2U/T1V/T2W/T3IM3~NOTE: Do not plug in a Modem or telepho

Page 52

3 VFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 3-3For VFDXXXSXXE PNP (source mode) B2U/T1V/T2W/T3IM3~NOTE: Do not plug in a Modem or tel

Page 53

VFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 3-4 3.2 External Wiring MotorOutput AC Line ReactorPower SupplyMagneticcontactorInput AC Line

Page 54 - Mx set d12

3 VFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 3-53.3 Main Circuit Wiring 1. Main Circuit Terminals DC ReactorRL1SL2TL3UT1VT2WT3B2B1+2+1

Page 55

VFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 3-6 2. Terminal Explanations Terminal Symbol Explanation of Terminal Function R/L1, S/L2, T

Page 57 - Reset counter

3 VFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 3-7B. XXXSXXE Multi-step speed 3** 1. Terminal Explanations: Terminal symbols Terminal nam

Page 58

VFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 3-8 3. During installation, follow all local electrical, construction, and safety codes for

Page 59

3 VFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 3-914. If a filter is required for reducing EMI (Electro Magnetic Interference), install i

Page 61

4 VFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 4-1 CHAPTER 4 DIGITAL KEYPAD OPERATION 4.1 Description of Digital Keypad This digital k

Page 62

VFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 4-2 4.2 Explanations of Display Messages Display Message Descriptions The AC drive Master

Page 63

4 VFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 4-3 4.3 Explanation of LED Indicators RUNFWDREVSTOPStop AC drive when STOP button has been

Page 64

VFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 4-4 4.4 Keypad Operation MODEMODEMODEMODEMODEMODEMODEPRO GDATAPRO GDATAPRO GDATAChange displa

Page 65 - Settings d20 to d150%

5 VFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-1CHAPTER 5 DESCRIPTION OF PARAMETER SETTINGS 5.1 Group 0: User Parameters 0 - 00

Page 66

VFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-2 0 - 03 Start-up Display Selection Factory Setting: d 0 Settings d 0

Page 67

VFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED TABLE OF CONTENTS CHAPTER 1 RECEIVING AND INSPECTION 1.1 Nameplate Information ...

Page 68

5 VFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-3 Display Number Represented 999 The absence of a decimal point indicates a three–dig

Page 69 - Output Frequency

VFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-4 0 - 08 Password Decode Factory Setting: d 0 Settings d 0 to d 999

Page 70

5 VFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-55.2 Group 1: Basic Parameters 1 - 00 Maximum Output Frequency (Fo. max) Factory

Page 71

VFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-6 1 - 03 Mid-Point Frequency (Fmid) Factory Setting: d 1.0 Settings d 1.0

Page 72

5 VFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-7 1 - 06 Minimum Output Voltage (Vmin) Factory Setting: d12.0* Settings

Page 73 - Computer

VFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-8 1 - 09 Acceleration Time 1 (Taccel 1) Factory Setting : d10.0 1 - 10 Deceleration

Page 74

5 VFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-91 - 13 Jog Acceleration/Deceleration Time Factory Setting: d 10.0 Set

Page 75 - ( 7.E.1)

VFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-10 1 - 15 Auto Acceleration / Deceleration Factory Setting: d 0 Settings

Page 76

5 VFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-11 1 - 18 Jog Decelerating Time Factory Setting: d0.0 Settings d0.0 to d600 When Pr.1-1

Page 77

VFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-125.3 Group 2: Operation Method Parameters 2 – 00 Source of Frequency Command Fac

Page 78

VFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED CHAPTER 5 DESCRIPTION OF PARAMETER SETTINGS 5.1 Group 0: User Parameters ...

Page 79

5 VFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-13J1Voltage signal input(0-10V)Current signal input(4-20mA)  When setting analog overl

Page 80

VFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-14HzFreq.MotorSpeedStops according to deceleration timeTimeHzFreq.MotorSpeedFree runningto

Page 81

5 VFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-152 - 04 Reverse Operation Factory Setting: d 0 Settings d 0 E

Page 82

VFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-165.4 Group 3: Output Function Parameters 3 - 00 Analog Output Signal Factory Settin

Page 83

5 VFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-17 3 - 02 Desired Frequency Attained Factory Setting: d 1.0 Settings

Page 84

VFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-18The timing diagram is shown below: Preliminary Counter Value Attained Output(Pr. 3-04=d3)

Page 85

5 VFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-19 Function Explanations: d 0 Not Used. d 1 AC drive operational: the output termin

Page 86

VFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-205.5 Group 4: Input Function Parameters 4 - 00 Potentiometer Bias Frequency Factor

Page 87

5 VFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-21Example 2: In this example with the potentiometer set to 0V the Output Frequency is 10

Page 88

VFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-22Example 5: In this example a 1 volt negative bias is used. In a noise environment, it

Page 89

VFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED B.5 Remote Controller RC-01...

Page 90 - Dwell (sleep) Function

5 VFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-23Example 8: In this example, the option of anti-slope is shown. Anti-slope is used in a

Page 91 - Display value of F, H

VFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-24 Explanations: d0 Parameter Disable: Enter value (d0) to disable any Multi-Function Inpu

Page 92

5 VFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-25d4, d5 External Faults: Parameter values d4, d5 programs Multi-Function Input Terminal

Page 93

VFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-26Freq.Step 1Step 2Step 3Step 4Step 5Step 6Step 7TimeOFFONONON ONON ONON ONONON ON ONONOper

Page 94

5 VFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-27d11 Acceleration/Deceleration Speed Inhibit: Parameter value d11 programs Multi-Functi

Page 95

VFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-28d13, d14 External Base Block: Parameter values d13, d14 program Multi-Function Input Term

Page 96

5 VFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-29d17, d18 PLC Function Control: Parameter value d17 programs Multi-Function Input Termi

Page 97

VFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-30d20 Counter Reset: Parameter value d20 programs Multi-Function Input Terminal: M1 (Pr.4-0

Page 98

5 VFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-315.6 Group 5: Multi-step Speed and PLC (Process Logic Control) Parameters 5 - 00 1s

Page 99

VFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-32Example 1 (Pr.5-07 = d1): Execute one cycle of the PLC program. Its relative parameter se

Page 100

1 VFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 1-1 If there is any nameplate information not corresponding to your purchase order or any

Page 101

5 VFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-33Example 2 (Pr.5-07 = d2): Continuously executes program cycles The diagram below shows

Page 102

VFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-34Example 4 (Pr. 5-07 =d 4) Continuously execute PLC cycles step by step: In this explana

Page 103

5 VFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-355 - 08 PLC Forward/Reverse Motion Factory Setting: d 0 Settings d 0

Page 104

VFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-365 - 09 Time Duration of Master Frequency Factory Setting: d 0 5 - 10 Time Dura

Page 105

5 VFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-375.7 Group 6: Protection Parameters 6 - 00 Over-Voltage Stall Prevention Fact

Page 106

VFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-386-02 Over-Current Stall Prevention Level Factory Setting: d130 Settings d20 to d150%

Page 107

5 VFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-396 - 04 Over-Torque Detection Level Factory Setting: d 150 Settings d 30

Page 108

VFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-406 - 08 Present Fault Record Factory Setting: d 0 6 - 09 Second Most Recent Fault

Page 109

5 VFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-415.8 Group 7: Motor Parameters 7 - 00 Motor Rated Current Factory Setting: d 85

Page 110 - STANDARD SPECIFICATIONS

VFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-425.9 Group 8: Special Parameters 8 - 00 DC Braking Voltage Level Factory Setting:

Page 112 - ACCESSORIES

5 VFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-432. DC Braking during stopping is used to decrease stopping time and also to hold a st

Page 113

VFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-44 Following a power failure, the AC drive will start its speed search operation, only if

Page 114

5 VFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-45reset/restart operation after any fault has occurred. When enabled, the AC drive will

Page 115

VFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-465.10 Group 9: Communication Parameters 9 - 00 Communication Address Factory

Page 116

5 VFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-47 9 - 03 Modbus Communication Watchdog Timer Factory Setting: d 0 Settings d0

Page 117 - EMI Filter (08TDT1W4S)

VFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-48 Code Meaning: ASCII mode: Each 8-bit data is the combination of two ASCII characters.

Page 118 - EMI Filter (20TDT1W4S)

5 VFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-492.2 11-bit character frame (For 8-bit character): Start bit0123456StopbitStopbit8-

Page 119 - EMI Filter (35DRT1W3C)

VFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-503.2 ADR (Communication Address) Valid communication addresses are in the range of 0 to 25

Page 120

5 VFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-51Command code: 06H, write 1 word For example, writing 6000(1770H) to address 0100H of A

Page 121 - VFD-S Programming

VFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-52Command code: 10H, write n word, n<=12 For example, writing 6000(1770H) to Pr 5-00 (ad

Page 122 - Unit: mm (inch)

2 VFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 2-1CHAPTER 2 STORAGE AND INSTALLATION 2.1 Storage The AC drive should be kept in the

Page 123 -

5 VFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-53RTU mode: Command message: Response message: ADR 01H ADR 01H CMD 10H CMD 10H

Page 124 - Dimensions

VFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-54RTU mode: ADR 01H CMD 03H 21H Starting address 02H 00H Number of data (count by word)

Page 125 - Unit: mm [inches]

5 VFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-55Unsigned int crc_chk(unsigned char* data, unsigned char length){ int j; unsigned i

Page 126 - Unit: mm [inch]

VFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-563.5 Address list: The contents of available addresses are shown as below: Content Addres

Page 127

5 VFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-57Content Address Functions Status monitor Read only 2100H 21: Reserved 22: CPU failure

Page 128

VFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-583.6 Exception response: Except for broadcast messages, the AC drive is been expected to r

Page 129

5 VFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-59The AC drive receives the messages, but detects a communication error, thus, no respon

Page 130

VFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-60#define MCR 0x0004 #define LSR 0x0005 #define MSR 0x0006 unsigned char rdat[60]; /*

Page 131

5 VFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-615.11 Group A: PID Parameters A - 00 PID Feedback Terminal Selection Factory

Page 132

VFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-62 A - 05 Integration’s Upper Bound Frequency Factory Setting: d100 Settings d0

Page 133

VFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 2-22.3 Installation Improper installation of the AC drive will greatly reduce its life. Be s

Page 134

5 VFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-63 A - 11 Revival Frequency Factory Setting: d0.0 Settings d0.0 to d400Hz

Page 135

VFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-64PA-02IA-03A-01++++Ta r ge tValueDetectionValue GainDA-04A-05A-07Integration's Upper

Page 136

6 VFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 6-1 CHAPTER 6 MAINTENANCE AND INSPECTIONS Modern AC drives are based on solid state el

Page 138

7 VFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 7-1 CHAPTER 7 TROUBLESHOOTING AND FAULT INFORMATION The AC drive has a comprehensive f

Page 139 - Unit: mm [inch

VFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 7-2 Fault Name Fault Descriptions Corrective Actions The AC drive detects excessive drive o

Page 140

7 VFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 7-3 Fault Name Fault Descriptions Corrective Actions Internal memory IC can not be progr

Page 142 - Amendment Directive 93/68/EEC

8 VFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 8-1 CHAPTER 8 SUMMARY OF PARAMETER SETTINGS !: The parameter can be set during operation,

Page 143 - EC Declaration of Conformity

VFD-S Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 8-2 Group 1 Basic Parameters Parameters Explanation Settings Factory Setting 1-00 Maximum