VFD-S Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
5-34
Example 4 (Pr. 5-07 =d 4) Continuously execute PLC cycles step by step:
In this explanation, the PLC program runs continuously step by step. Also shown are
examples of steps in the Reverse direction.
Frequency
60Hz
50Hz
40Hz
30Hz
20Hz
15Hz
10Hz
0Hz
Time
(Sec)
FWD
REV
t
5-09
Master freq.=5Hz
5-00=10 Hz
5-01=20 Hz
5-02=40 Hz
5-03=60 Hz
5-04=50 Hz
5-05=30 Hz
5-06=15 Hz
4-07=d17
3-05=d10
3-06=d11
5-07=d4
5-08=d68
5-09=10
5-10=10
5-11=12
5-12
Sec
Sec
Sec
=15 Sec
5-13=15 Sec
5-14=8 Sec
5-15=17 Sec
5-16=17 Sec
Example 5 (Pr. 5-07 = d1 Execute one cycle of the PLC program):
In this example, the PLC program runs continuously. It should be noted that the times of
reserve motion may be shorter than expected, due to the acceleration/deceleration times.
Frequenc
y
60Hz
50Hz
40Hz
30Hz
20Hz
15Hz
10Hz
0Hz
Time
(Sec)
FWD
REV
5-09
Master freq.=5Hz
5-00=10 Hz
5-01=20 Hz
5-02=40 Hz
5-03=60 Hz
5-04=50 Hz
5-05=30 Hz
5-06=15 Hz
4-07=d17
3-05=d10
3-06=d11
5-07=d1
5-08=d68
5-09=10
5-10=10
5-11=12
5-12
Sec
Sec
Sec
=15 Sec
5-13=15 Sec
5-14=8 Sec
5-15=17 Sec
5-16=17 Sec
* The calculation of time for Pr.5-11, Pr.5-12, Pr.5-15 and Pr.5-16 should be carefully planned.