Delta-electronics Network Device DOP-A/AE/AS Manuel d'utilisateur Page 97

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 137
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 96
Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series
1-96 Revision January, 2008, Doc. Name: 2007PDD23000007
C. Connections (Connector Pinouts)
RS-232
DOP
9 pin D-SUB male (RS-232)
Controller
9 pin D-SUB male (RS-232)
Controller
9 pin D-SUB male (RS-232)
RXD (2)
(3) TXD
TXD (3)
GND (5)
(2) RXD
(5) GND
Top View
RS-422
DOP
9 pin D-SUB male (RS-422)
Controller
9 pin D-SUB male (RS-422)
Controller
9 pin D-SUB male (RS-422)
RXD- (1
)
(7)T
-
RXD+ (2)
TXD+ (3)
(8)T+
(6)R+
TXD- (4) (1)R-
Top View
RS-485
DOP
9 pin D-SUB male (RS-485)
DOP
9 pin D-SUB male (RS-485)
DOP
9 pin D-SUB male (RS-485)
D+ (2
)
T+ (8)
D+ (3)
D- (1)
T-( 7)
D- (4)
Top View
NOTE
1) The valid station number is in the range of 11 to 99. However, 20, 30, 40, 50, 60, 70, 80 and 90 cannot
be used as they are all broadcast station number.
00 for all broadcast
10 for the broadcast to 11 ~ 19
20 for the broadcast to 21 ~ 29
and vise versa.
2) Now the broadcast function is not provided, therefore, 20, 30, 40, 50, 60, 70, 80 and 90 cannot be used.
Pin1