Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series
Revision January, 2008, Doc. Name: 2007PDD23000007 1-107
Modicon TSX Micro (Modbus RTU) Back to Table
A. HMI factory settings
Baud rate: 9600, 8, ODD, 1.
Controller station number: 2.
Control area/status area: %MW0 / %MW10.
NOTE
1) HMI must select Modbus (Master) --- 984 RTU as the communication mode.
2) The communication mode of PLC should be switched to Modbus Slave by using PL7 software.
B. Connections (Connector Pinouts)
RS-485
DOP
9 pin D-SUB male (RS-485)
Controller
8 pin Mini DIN male (RS-485)
Controller
8 pin Mini DIN male
(RS-485)
RXD+ (2
)
(1) D+
TXD+ (3)
RXD- (1)
TXD- (4)
(2) D-
(5)
(7)
Top View
7
1
2
5
7
Vue de la page 107