VFD-V Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
Preface
Thank you for choosing DELTA’s high-performance VFD-V Series. VFD-V Series
are manufactured by adopting high-quality components, material and incorporating the
latest microprocessor technology available.
Getting Started
This manual will be helpful in the installation, parameter setting, troubleshooting, and daily
maintenance of the AC motor drives. To guarantee safe operation of the equipment, read
the following safety guidelines before connecting power to the AC drives. Keep this
operating manual handy and distribute to all users for reference.
!
WARNING
!
Always read this manual thoroughly before using VFD-V series AC Motor Drives.
!
DANGER! AC input power must be disconnected before any maintenance. Do not
connect or disconnect wires and connectors while power is applied to the circuit.
Maintenance must be performed by qualified technicians.
!
CAUTION! There are highly sensitive MOS components on the printed circuit boards.
These components are especially sensitive to static electricity. To avoid damage to
these components, do not touch these components or the circuit boards with metal
objects or your bare hands.
!
DANGER! A charge may still remain in the DC-link capacitor with hazardous voltages
even if the power has been turned off. To avoid personal injury, please ensure that
power has turned off before operating AC drive and wait ten minutes for capacitors to
discharge to safe voltage levels.
!
CAUTION! Ground the VFD-V using the ground terminal. The grounding method must
comply with the laws of the country where the AC drive is to be installed. Refer to Basic
Wiring Diagram.
!
DANGER! The AC drive may be destroyed beyond repair if incorrect cables are
connected to the input/output terminals. Never connect the AC drive output terminals
U/T1, V/T2, and W/T3 directly to the AC main circuit power supply.
!
CAUTION! The final enclosures of the AC drive must comply with EN50178. (Live parts
shall be arranged in enclosures or located behind barriers that meet at least the
requirements of the Protective Type IP20. The top surface of the enclosures or barrier
that is easily accessible shall meet at least the requirements of the Protective Type
IP40). (VFD-V series corresponds with this regulation.)
CAUTION! Heat sink may heat up over 70
o
C (158
o
F), during the operation. Do not
touch the heat sink.
CALL NOW 800-985-6929
http://www.automatedpt.com
CALL NOW 800-985-6929
http://www.automatedpt.com
Vue de la page 0
1 2 3 4 5 6 ... 181 182

Résumé du contenu

Page 1 - Preface

VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED Preface Thank you for choosing DELTA’s high-performance VFD-V Series. VFD-V Series are ma

Page 2

VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 3-23.1 Basic Wiring Diagram For wiring of the inverter, it is divided into the main circuit a

Page 3

VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-72Definition Parameter Address Function 2104H output current (XX.XX) 2105H DC-BUS vo

Page 4

5 VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-73Meaning of the Error Codes: Error Codes Explanations 1 Data Contents Error: If the v

Page 5 - 1.2 Model Explanation

VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-745.11 Group 10: Speed Feedback Parameter 10-00 PG (encoder) Pulses Factory setting 6

Page 6 - 037V23A0T 0 10 9999

5 VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-75Phase B is a forward run pulse, then phase A is High. Phase A is a reverse run pulse

Page 7 - 2.1 Storage

VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-76 This parameter determines the PG feedback filter time for the AC drive to process the m

Page 8 - 2.2 Installation

5 VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-77IP05-21+-++05-2305-2205-2405-2510-0510-0601-10Motor10-0410-0710-0810-00 10-0105-05 0

Page 9 - CHAPTER 3 WIRING

VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-78Phase A is a forward run pulse, then phase B is High. Phase B is a reverse run pulse, t

Page 10 - 3.1 Basic Wiring Diagram

5 VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-7910-18 Loop Speed a Factory setting 1.00 Settings 0.00~400.00 Hz 10-19 Loop Point a

Page 11

VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-80 There are speed LOOP and position LOOP in position mode. This parameter is used to adju

Page 12

5 VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-81 10-32 REV Limit of Absolute P2P aFactory setting 0 Settings 0: No Limit 1~60000 

Page 13 - 3.2 External Wiring

3 VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 3-3Wiring Diagram 2 15HP(11kW) and above AVIACIAUIACM4~20mA-10~+10V+10V5K321Power supply+1

Page 14

VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-82 The distance that each pulse moves (mm) should use with 10-33~10-40 (8-point P2P comman

Page 15

6 VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 6-1CHAPTER 6 MAINTENANCE AND INSPECTIONS Modern AC drives are based on solid state ele

Page 16 - 3.5 Component Explanations

CALL NOW 800-985-6929http://www.automatedpt.comEmail: [email protected] NOW 800-985-6929http://www.automatedpt.comEmail: charles@automatedp

Page 17

7 VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 7-1CHAPTER 7 ERROR MESSAGE AND TROUBLESHOOTING The AC drive has a comprehensive fault d

Page 18 - S/L2 T/L3

VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 7-2Code Displayed Error Explanations Treatments OL: AC drive overload Output current excee

Page 19

7 VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 7-3Code Displayed Error Explanations Treatments Over-current during decel  Check wheth

Page 20

VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 7-4Code Displayed Error Explanations Treatments AC drive’s detection circuit fault  Retur

Page 21

7 VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 7-5Code Displayed Error Explanations Treatments R1 setting error  Re-do the setting or

Page 22 - 3.6 Wiring Notice

CALL NOW 800-985-6929http://www.automatedpt.comEmail: [email protected] NOW 800-985-6929http://www.automatedpt.comEmail: charles@automatedp

Page 23

8 VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 8-1CHAPTER 8 PARAMETER SUMMARY Group 0: System Parameter Control Mode Parameters Func

Page 24

VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 3-4Wiring of SINK mode and SOURCE mode FWDREVMI1MI2MI3MI4MI6MI5DCM+24VFWD/STOPREV/STOPMulti-s

Page 25

VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 8-2Control Mode Parameters Functions Settings Factory Setting VF VG SV SG T TGa 00-04 Defin

Page 26

8 VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 8-3Control Mode Parameters Functions Settings Factory Setting VF VG SV SG T TGa 00-04 De

Page 27 - VFD-PU05 Operation Flow Chart

VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 8-4Control Mode Parameters Functions Settings Factory Setting VF VG SV SG T TGa 00-12 Const

Page 28

8 VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 8-5Control Mode Parameters Functions Settings Factory Setting VF VG SV SG T TGa 00-20 So

Page 29

VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 8-6Group 1: Basic Parameter Control Mode Parameters Functions Settings Factory Setting VF

Page 30

8 VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 8-7Control Mode Parameters Functions Settings Factory Setting VF VG SV SG T TGa 01-19 Th

Page 31

VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 8-8Group 2: Digital Output/Input Parameter Control Mode Parameters Functions Settings Fact

Page 32

8 VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 8-9Control Mode Parameters Functions Settings Factory Setting VF VG SV SG T TG18: operat

Page 33

VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 8-10Control Mode Parameters Functions Settings Factory Setting VF VG SV SG T TGa 02-07 UP/D

Page 34

8 VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 8-11Control Mode Parameters Functions Settings Factory Setting VF VG SV SG T TG17: PCO R

Page 35 - V/F Mode bit=1

3 VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 3-53.2 External Wiring MotorOutput AC Line ReactorPower SupplyMagneticcontactorInput AC L

Page 36

VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 8-12Control Mode Parameters Functions Settings Factory Setting VF VG SV SG T TGa 02-19 Pre-

Page 37

8 VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 8-13Group 3: Analog Output/Input Parameter Control Mode Parameters Functions Settings F

Page 38 - The maximum output voltage

VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 8-14Control Mode Parameters Functions Settings Factory Setting VF VG SV SG T TGa 03-08 (AUI

Page 39

8 VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 8-15Control Mode Parameters Functions Settings Factory Setting VF VG SV SG T TG15: magne

Page 40

VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 8-16Group 4: Multi-Step Speed and Process Control Operation (PCO) Parameter Control Mode Pa

Page 41

8 VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 8-17Control Mode Parameters Functions Settings Factory Setting VF VG SV SG T TGa 04-27 T

Page 42 - V/F Curve

VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 8-18Control Mode Parameters Functions Settings Factory Setting VF VG SV SG T TGa 04-34 Mult

Page 43

8 VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 8-19Group 5: Motor Parameter Control Mode Parameters Functions Settings Factory Setting

Page 44

VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 8-20Control Mode Parameters Functions Settings Factory Setting VF VG SV SG T TG 05-18 LM o

Page 45 - 01-25 01-26

8 VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 8-21Group 6: Protection Parameter Control Mode Parameters Functions Settings Factory Se

Page 46

VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 3-63.3 Main Circuit Terminal Explanations Terminal Symbol Content Explanation R/L1, S/L2, T/

Page 47

VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 8-22Control Mode Parameters Functions Settings Factory Setting VF VG SV SG T TGa 06-09 Over

Page 48

8 VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 8-23Control Mode Parameters Functions Settings Factory Setting VF VG SV SG T TG5: oL1 (e

Page 49

VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 8-24Group 7: Special Parameter Control Mode Parameters Functions Settings Factory Setting

Page 50

8 VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 8-25Control Mode Parameters Functions Settings Factory Setting VF VG SV SG T TGa 07-12 S

Page 51

VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 8-26Group 8: High-Performance Parameter Control Mode Parameters Functions Settings Factor

Page 52

8 VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 8-27Group 9: Communication Parameter Control Mode Parameters Functions Settings Factor

Page 53

VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 8-28Group 10: Speed Feedback Parameter Control Mode Parameters Functions Settings Factory

Page 54

8 VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 8-29Control Mode Parameters Functions Settings Factory Setting VF VG SV SG T TGa10-05

Page 55

VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 8-30Control Mode Parameters Functions Settings Factory Setting VF VG SV SG T TGa 10-15 Diff

Page 56

8 VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 8-31Control Mode Parameters Functions Settings Factory Setting VF VG SV SG T TGa 10-37

Page 57

3 VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 3-7Terminal Symbol Explanation on the Terminal Function Factory Setting MO2 Multi-functi

Page 58

CALL NOW 800-985-6929http://www.automatedpt.comEmail: [email protected] NOW 800-985-6929http://www.automatedpt.comEmail: charles@automatedp

Page 59

AVFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED A-1Specifications 230V Class 230V Class Model Number VFD-xxxV23A 007 015 022 037 055 075 11

Page 60

VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED A-2460V Class 460V Class Model Number VFD-xxxV43x 007 015 022 037 055 075 110 150 185 220 300

Page 61

BVFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED B-1ACCESSORIES B.1 Non-fuse Circuit Breaker Chart Per UL 508C, paragraph 45.8.4, part a,

Page 62

VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED B-2Line Fuse Model Input Current (A) Output Current (A)I (A) Bussmann P/N VFD185V43A 39 38

Page 63

BVFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED B-3B.2 All Braking Resistors & Braking Units Use in AC Drives Note: Please only use DEL

Page 64

VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED B-4Braking Resistors & Braking Units CALL NOW 800-985-6929http://www.automatedpt.comEma

Page 65

BVFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED B-5Braking Resistors & Braking Units CALL NOW 800-985-6929http://www.automatedpt.com

Page 66

VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED B-6Braking Resistors & Braking Units Braking resistors model no.: BR1K0W050, BR1K2W008

Page 67

BVFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED B-7B.3 AMD - EMI Filter Cross Reference EMI Filter with choke Model of AC Motor Drive Filt

Page 68

VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 3-83.5 Component Explanations 1 HP to 5 HP (VFD007V23A/43A, VFD015V23A/43A, VFD022V23A/43A, V

Page 69

VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED B-8EMI Filters (26TDT1W4C) Use on 1-5 HP, 230V, Three phase Models EMI Filters (15TDT1W4

Page 70

BVFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED B-9EMI Filters (50TDS4W4V4) Use on 7.5-10HP/230V, VFD110V43A, Three phase Models EMI

Page 71

VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED B-10EMI Filters (50TDS4W4C) Use on 20-25 HP, 430V, Three phase Models EMI Filters (100TD

Page 72 - Speed Feedback

BVFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED B-11EMI Filters (150TDS84C) Use on 25-40 HP, 230V & 60HP, 430V, Three phase Models

Page 73

VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED B-12EMI Filters (200TDDS84C) Use on 100 HP, 430V, Three phase Models CALL NOW 800-985-692

Page 74 - Input voltage

BVFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED B-13B.4 PG Card Wiring Diagram NFBR/L1S/L2T/L3U/T1V/T2W/T3M3~MotorPGAB12V0VPG-03VFD-V+12VGN

Page 75

VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED B-14B.4.1 Explanations on the PG Card Terminals Terminals Explanation 12V Power Supply of the

Page 76

BVFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED B-15B.4.3 Exterior of PG-03 Fj1OCTPA/OB/O0V12V0VAABConnect to theSeries Control Board VFD-V

Page 77 - 06-08, 06-11

VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED B-16B.4.5 VFD-V & VFD-B Series Speed Regulation Comparison VFD-V VFD-B Sensorless-Vecto

Page 78

BVFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED B-17B.5 Zero Phase Reactor (RF220X00A) Dimension Motor HP kW Qty. Recommended Wire

Page 79 - Op stall low limit

3 VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 3-97.5 HP to 15 HP (VFD055V23A/43A, VFD075V23A/43A, VFD110V43B) POWER IMMOTOR3 Control T

Page 80

CALL NOW 800-985-6929http://www.automatedpt.comEmail: [email protected] NOW 800-985-6929http://www.automatedpt.comEmail: charles@automatedp

Page 81

CVFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED C-1 DIMENSIONS VFD007V23A/43A Unit: mm (inches) 260.0 [10.24]135.0 [5.32] 160.2 [6.31]150.

Page 82 - RUN/STOP

VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED C-2VFD015V23A/43A VFD022V23A/43A Unit: mm (inches) R3.25[R0.13]6.5 [0.26]6.5[0.26]11.3 [0.

Page 83

CVFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED C-3 VFD037V23A/43A Unit: mm (inches) 6.5[0.26]R3.25[R0.13]6.5 [0.26]28.0[1.10](2X)34.0[1.

Page 84

VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED C-4VFD055V23A/43A VFD075V23A/43A VFD110V43B Unit: mm (inches) 183.2 [7.22]7.0[0.28]R3.5 [R0.

Page 85

CVFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED C-5 VFD110V23A/43A VFD150V23A/43A VFD185V23A/43A VFD220V23A/43A Unit: mm (inches) 13.0 [0.

Page 86

VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED C-6VFD300V23A VFD370V23A Unit: mm (inches) 335.0 [13.19]370.0 [14.57] 260.0 [10.24]589.0 [2

Page 87

CVFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED C-7 VFD300V43A VFD370V43A VFD450V43A Unit: mm (inches) R6.5[0.25]13.0[0.51]21.0[0.83]335.0

Page 88

VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED C-8VFD550V43A VFD750V43A Unit: mm (inches) R6.5[0.25]280.0 [11.02]660.0 [25.98]631.0 [24.84]

Page 89

CVFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED C-9 The Apparatus Size of the Digital Hand-Held Programming Panel VFD-PU05 Unit: mm (inches

Page 90 - Fan control

VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 3-1015HP to 30HP (VFD110V23A/43A, VFD150V23A/43A, VFD185V23A/43A, VFD220V23A/43A) R/L1DC DC +

Page 91

CALL NOW 800-985-6929http://www.automatedpt.comEmail: [email protected] NOW 800-985-6929http://www.automatedpt.comEmail: charles@automatedp

Page 92

DVFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED D-1 DELTA ELECTRONICS, INC. EC Declaration of Conformity According to the Low Volta

Page 93

VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED D-2 DELTA ELECTRONICS,INC. EC Declaration of Conformity According to the Electromagnet

Page 94

3 VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 3-1140 to 50 HP 230V (VFD300V23A, VFD370V23A) W/T3S/L2R/L1 T/L3 +2+1 U/T1 V/T2(173in-lbf)S

Page 95

VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED CHAPTER 1 RECEIVING AND INSPECTION 1.1 Nameplate Information ...

Page 96

VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 3-1240HP to 60HP 460V (VFD300V43A, VFD370V43A, VFD450V43A) R/L1+1+2-S/L2 T/L3 U/T1 V/T2 2/T3P

Page 97

3 VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 3-1375-100 HP 460V (VFD550V43A, VFD750V43A) POWER 200kgf-cmScrew Torque:MOTORV/T2U/T1+2+1R

Page 98

VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 3-143.6 Wiring Notice 1. There are corresponding ring terminals which will be included with

Page 99

3 VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 3-1510. Be sure of the power voltage and the greatest current possible supplied. 11. When

Page 100 - VFD-V Series

CALL NOW 800-985-6929http://www.automatedpt.comEmail: [email protected] NOW 800-985-6929http://www.automatedpt.comEmail: charles@automatedp

Page 101

4 VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 4-1CHAPTER 4 DIGITAL KEYPAD (VFD-PU05) OPERATION 4.1 Description of the Digital Keypad

Page 102

VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 4-2Messages Displayed Descriptions Output current Parameter duplication function: press PR

Page 103

4 VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 4-34.3 Operation steps of the Digital Keypad VFD-PU05 XX XX-XXXXXXX-END-VFD-PU05 Op

Page 104

CALL NOW 800-985-6929http://www.automatedpt.comEmail: [email protected] NOW 800-985-6929http://www.automatedpt.comEmail: charles@automatedp

Page 105

5 VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-1CHAPTER 5 DESCRIPTION OF PARAMETER SETTINGS 5.1 Group 0: System Parameter 00-00 Ide

Page 106

VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5.6 Group 5: Motor Modulation Parameter ...

Page 107 - 02-11~02-14 set 31

VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-2 00-02 Parameter Reset Factory setting 0 10 Parameter reset (for 60Hz input) Settings

Page 108

5 VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-3 00-03 Start-up Display of the Drive a Factory setting 0 Settings 0 F (Master f

Page 109

VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-444 torque limit (Pr. 06-12) 45 the q axis current (V/F and vector) 46 Frequency of Enco

Page 110

5 VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-5 Pr. 00-07: This parameter allows the user to input their password and disable the par

Page 111

VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-6 Bit1 = This setting allows the frequency/torque commands of PU05 and RS485 to either be

Page 112

5 VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-74: Torque control: Enables Torque (current) Control. Torque control allows the user to

Page 113

VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-8 This parameter may also be used in Vector control to determine if the drive will skip th

Page 114

5 VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-900-15 Carrier Frequency Upper Bound a Factory setting 10 Settings 0: soft pwm 1~15

Page 115

VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-10 If the carrier frequency’s lower bound (Pr. 00-16) > the carrier frequency’s upper b

Page 116

5 VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-1100-20 Source of the Frequency Command aFactory setting 0 Settings 0 The digital key

Page 117

CALL NOW 800-985-6929http://www.automatedpt.comEmail: [email protected] NOW 800-985-6929http://www.automatedpt.comEmail: charles@automatedp

Page 118

VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-12Ramp to stop: The drive will ramp down from maximum output frequency (Pr. 01-00) to minim

Page 119

5 VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-135.2 Group 1: Basic Parameter 01-00 Maximum Output Frequency Factory setting 60.00/

Page 120

VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-14 When setting the V/F curve, please follow this hierarchy for frequency: 01-01≥01-03≥01-

Page 121

5 VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-1501-12 1st Acceleration Time aFactory setting 10.00/60.00 01-13 1st Deceleration Tim

Page 122

VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-1601-00Maximum Operation FrequencySet Point of the OperationFrequencyTime01-12 01-1401-

Page 123

5 VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-17Frequency1st/4th Acceleration/Deceleration Switching01-234th Acceleration Time4th Dece

Page 124

VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-1801-28 Skip Frequency 1 (upper limit) Factory setting 0.00 01-29 Skip Frequency 1 (lower

Page 125

5 VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-195.3 Group 2: Digital Output/Input Parameter 02-00 2-Wire/3-Wire Operation Control F

Page 126

VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-2002-01 Multi-Function Input Command 1 (MI1) (NOTE 1) Factory setting 1 02-02 Multi-Func

Page 127

5 VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-21Settings Functions Explanations 7 Acceleration/deceleration Speed Inhibit When the a

Page 128

1 VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 1-1CHAPTER 1 RECEIVING AND INSPECTION This VFD-V AC drive has gone through rigorous qua

Page 129

VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-22Settings Functions Explanations 21 Digital Down Command 22 Auto procedural operation fu

Page 130

5 VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-23Settings Functions Explanations 40 P2P Hold P2P is pause. AC drive keeps outputting a

Page 131 - { { { { { {

VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-2402-10 Digital Input Operation Direction a Factory setting 0 Settings 0~65535 Bit 0~7

Page 132

5 VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-25Settings Functions Explanations 21 Pre-set counter value attained Please refer to 02-

Page 133

VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-26Example: If Pr.02-10 is 1 (AC Drive running), and Relay 1 is set to N.O., then R1 close w

Page 134

5 VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-27Desired Counter ValueAttained outputPreset Counter ValueAttained output0.5msDisplay(Pr

Page 135

VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-285.4 Group 3: Analog Output/Input Parameter 03-00 Analog Input 1 (AVI) aFactory setting

Page 136

5 VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-2903-06 (AVI) Positive/Negative Bias Mode aFactory setting 0 Settings 0 zero bias 1

Page 137

VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-3003-09 Analog Input 1 Gain (AVI) aFactory setting 100.0 Settings -500.0~+500.0% 03-10 A

Page 138

5 VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-31Example 3: 60Hz0V10V03-06=103-09=03-039V5096010X100%=92.5%50960X=X=10.89-10.8=-1.810Hz

Page 139

VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 1-21.3 Serial Number Explanation ●Please contact the dealers immediately should any discrep

Page 140

VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-32Example 7: 60Hz0V03-03=503-06=310V120206010X100%=200%5V Example 8: 60Hz10V03-03=1003-06=

Page 141

5 VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-3303-13 Analog Input Noise Filter aFactory setting 0.10 Settings 0.00~2.00 Sec  Interf

Page 142

VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-34Settings Functions Explanations 16 Q-axis voltage command 200V (400V) =100% 17 D-axis vo

Page 143

5 VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-35If the meter reads full scale at a voltage less than 10 volts, then Pr.03-16 should be

Page 144

VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-365.5 Group 04: Multi-Step Speed and Process Control Operation (PCO) 04-00 The 1st Step S

Page 145

5 VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-3704-15 Time Duration of the PCO Master Speed aFactory setting 0 04-16 Time Duration

Page 146

VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-38123456789101112131415 0WeightsBit0=Forward1=ReverseDirection of Pr.04-001st speed for Di

Page 147

5 VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-3904-33 Process Control Operation Mode a Factory setting 00000 Bit setting 0 directio

Page 148

VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-4004-35 Disable Skip Frequency Width a Factory setting 0.00 Settings 0.00~400.00Hz 04-36

Page 149

5 VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-415.6 Group 5: Motor Parameters 05-00 Motor Auto Tuning Factory setting 0Settings 0 n

Page 150

2 VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 2-1CHAPTER 2 STORAGE AND INSTALLATION 2.1 Storage The AC drive should be kept in the s

Page 151 - Specifications

VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-426. Set Pr.00-10 = 2~5 after any errors are eliminated. If needed, now adjust other par

Page 152

5 VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-4305-05 Number of Poles for Motor 1 Factory setting 4 Settings 2~20  This parameter

Page 153 - ACCESSORIES

VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-4405-19 LC of Motor 2 Factory setting XX Settings MH 05-20 Iron Loss of Motor 2 aFacto

Page 154

5 VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-4505-26 Low-Speed Excitation Magnet Compensation aFactory setting 10 Settings 0~100%

Page 155

VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-465.7 Group 6: Protection Parameter 06-00 Low Voltage Level Settings 160~220V aFactory s

Page 156

5 VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-47 06-02 Phase-Loss Protection aFactory setting 0 Settings 0 warn and keep operating

Page 157

VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-48 06-04 Over-Current Stall Prevention during Operation aFactory setting 170 Settings 10

Page 158

5 VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-4906-08 Over-Torque Detection Time (oL2) aFactory setting 0.1 Settings 0.0-60.0 Secon

Page 159

VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-5006-12 Over-Torque limit aFactory setting 150 Settings 0~250%  This parameter sets the

Page 160

5 VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-51 06-16 Op stall low limit aFactory setting 120 Settings 0~250% 06-17 Most Recent F

Page 161

VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 2-22.2 Installation CAUTION The control, power supply and motor leads must be laid separatel

Page 162

VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-52 28 pid error 29 ACI error 30 P2P Over Limit 31 CC 33 VEC R1 out of range (Pr. 05-30)

Page 163

5 VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-535.8 Group 7: Special Parameter 07-00 Software Braking Level Settings 350.0~450.0VDC

Page 164

VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-54Output FrequencyTimeONOFFRUN/STOPStartup Frequency01-09  This parameter determines the f

Page 165 - B.4 PG Card

5 VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-5507-06 Re-activate after Momentary Power Loss aFactory setting 0 Settings 0 disable

Page 166

VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-56OutputFrequencyOutputVoltage07-0807-0707-06=0107-0807-0707-06=02InputPowerMaximum Allowab

Page 167

5 VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-5707-12 Speed Search Type aFactory setting 0 Settings 0 speed search disabled 1 spee

Page 168

VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-5807-15 Gear Gap Acceleration-Interruption Time aFactory setting 0.00 Settings 0.00~400.

Page 169 -

5 VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-595.9 Group 8: High-Performance Parameter 08-00 PID Feedback Terminal Selection aFact

Page 170

VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-6008-05 PID Frequency Output Command limit aFactory setting 100.0 Settings 0.0~100.0%  T

Page 171 - DIMENSIONS

5 VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-61 PD Control: when deviation occurred, the system will immediately generate some opera

Page 172

3 VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 3-1CHAPTER 3 WIRING DANGER Hazardous Voltage Before accessing the AC drive:  Discon

Page 173

VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-62 These parameters determine Dwell (sleep) functions of the AC drive. If the command f

Page 174

5 VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-635.10 Group 9: Communication Parameter 09-00 Communication Address aFactory setting

Page 175

VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-64Settings Function Settings Function 0 7, N, 1 for ASCII 9 8, O, 1 for ASCII 1 7, N, 2

Page 176 - R6.5[0.25]

5 VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-65Start bit0123456StopbitStopbitData Format 7.N.2Start bit0123456EvenparityStopbitData

Page 177

VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-66The ASCII Mode: STX Start Word = ‘:’ (3AH) Address Hi Address Lo Communication Address:

Page 178

5 VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-673.3 Function Code and Data Contents 03H: read the contents of the register 06H: write

Page 179 - VFD-PU05

VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-68The RTU Mode: Inquiry message: Response message: Address 01H Address 01H Function 0

Page 180

5 VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-69The RTU Mode: Inquiry message: Response message: Address 01H Address 01H Functio

Page 181

VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-70unsigned int crc_chk(unsigned char* data, unsigned char length) { int j; unsigned int

Page 182

5 VFD-V Series DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED 5-71Definition Parameter Address Function Command toward the drive Bit8~9 00B: no functi