Ethernet Communication Module DVPEN01-SL
K100
K1TOP
K100TOP K1 K1
K0
K100
K1TOP
K100TOP
K1
H0
K6
K125
K119
K116
K115
SET M2
M1RST
MOV K0 D0= D0 K2
INC D0
END
K100 K1
M2
D14
RST M2
RST M2
= D14 K2
= D14 K3
FROM K116
Explanations:
The data exchange will be executed every one second.
Write the IP address of PLC_A into CR#117 and CR#118. The first two IP codes (192.168=H’C0A8) should
be written into CR#118, and the last two IP codes (0.4=H’0004) into CR#117.
Set CR#111 as “1” to enable the 8-bit mode. The MODBUS instruction is stored in the low byte of
CR#120~CR#247.
Write MODBUS instruction into CR#120~CR#125. CR#120 is the MODBUS address.
Write the length of the instruction into CR#119.
Write “1” into CR#115 to start the execution of MODBUS TCP instruction.
CR#116=2 refers to successful execution. CR#116=3 refers to failed execution.
If the execution is successful, Y0 on PLC_A will go between On and Off every one second.
DVP-PLC Operation Manual
57