Delta-electronics Network Device VFD-S Manuel d'utilisateur Page 12

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 22
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 11
English- 12
Pr. Explanation Settings
Factory
Setting
NOTE
2-00
Source of Master Frequency
Command
d5: Master Frequency operated by
RS-485 serial communication
interface and won’t record
frequency before power loss.
(won’t record the frequency of
power loss and it can do analog
overlap plus)
d0
2-01
Source of Operation
Command
d0: Digital Keypad
d1: External terminals. Keypad
STOP/RESET enabled.
d2: External terminals. Keypad
STOP/RESET disabled.
d3: RS-485 serial communication
(RJ-11) .Keypad STOP/RESET
enabled.
d4: RS-485 serial communication
(RJ-11). Keypad STOP/RESET
disabled.
d0
2-02 Stop Method
d0: STOP: ramp to stop; E.F.: coast
to stop
d1: STOP: coast to stop; E.F.: coast
to stop
d0
2-03 PWM Carrier Frequency Selections
d3: 3KHz
d4: 4KHz
d5: 5KHz
d6: 6KHz
d7: 7KHz
d8: 8KHz
d9: 9KHz
d10: 10KHz
d10
2-04 Motor Direction Control
d0: Enable forward/reverse
operation
d1: Disable reverse operation
d0
2-05 Loss of ACI Signal
d0: Decelerate to 0 Hz
d1: Coast to stop and display “EF”
d2: Continue operation by last
frequency command
d0
2-06 Analog Auxiliary Frequency Operation
d0: Disable
d1: Enable + AVI
d2: Enable + ACI
d0
Group 3 Output Function Parameters
Pr. Explanation Settings
Factory
Setting
NOTE
3-00 Analog Output Signal
d0: analog frequency meter
d1: analog current meter
d0
a3-01 Analog Output Gain d1 to d200% d100
3-02 Desired Frequency Attained d1.0 to d400 Hz d1.0
3-03 Terminal Count Value d0 to d999 d0
3-04 Preliminary Count Value d0 to d999 d0
3-05
Multi-Function Output Terminal 1
(Photocoupler Output)
d0: No Function d1
Vue de la page 11