Delta-electronics Modbus TCP Remote I/O Communication Module RTU-EN0 Manuel d'utilisateur Page 45

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 52
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 44
Modbus TCP Remote I/O Communication Module RTU-EN01
DVP-PLC Operation Manual
43
7.16 Smart PLC: Timer
Application
Setting up Smart PLC functions by DCISoft. After RY0 is On for 1 second, it will turn Off for 500
ms. This will repeat in cycle.
Steps
(1) Set up the timer: Timer 0 1s, Timer 1 500ms.
(2) Set up IF-THEN: When the timing reaches the target, RY0 will be On or Off.
1. Open the setup page and switch to “Smart PLC” page. Further switch to the “Timer” page.
2. Check to “Enable” Timer 0 and Timer 1 and set Timer 0 to “1s” and Timer 1 to “500ms”. Click “Apply” to
write the settings into RTU-EN01.
Vue de la page 44
1 2 ... 40 41 42 43 44 45 46 47 48 49 50 51 52

Commentaires sur ces manuels

Pas de commentaire